630A/800A Invicta 3 Panelboards
The last few years have seen a major change in the design and installation of commercial electrical distribution systems. The panelboard is at the heart of such a system, whether acting as the main incoming board or as part of the sub distribution. Modern electrical distribution systems have more RCD protection, more metering and more control devices. Panelboards have to offer a flexible solution to help meet these needs.
630A/800A Incoming 125A Outgoing - Glazed
Construction
- Enclosures manufactured from 1.5mm DC01M cold reduced mild steel, phosphate pretreated and powder coated to 00A01 BS4800.
- Removable gland plates are provided top and bottom for ease of installation.
- The removal of the gland plates and cable spreader also allows the mounting of DIN rail extension boxes and meter packs.
- Complies with BS EN 60439-1.
- Enclosure degree of protection IP3X.
- 1 & 3 pole MCCB 70mm² flexible.
- 1 & 3 pole MCCB 95mm² solid.
- Internal separation form 3A.
- 8, 12, 18 TP outgoing ways.
- Busbar rated current: 800A
- Busbar rated short time withstand current 35kA for 1x direct connection (unconditional).
- Single pole up to 125A - 70mm² flexible.
- Single pole up to 125A - 95mm² solid.
- Triple pole up to 250A -120mm² flexible.
630A/800A Incoming 125A Outgoing - Plain
Construction
- Enclosures manufactured from 1.5mm DC01M cold reduced mild steel, phosphate pretreated and powder coated to 00A01 BS4800.
- Removable gland plates are provided top and bottom for ease of installation.
- The removal of the gland plates and cable spreader also allows the mounting of DIN rail extension boxes and meter packs.
- Complies with BS EN 60439-1.
- Enclosure degree of protection IP3X.
- 1 & 3 pole MCCB 70mm² flexible.
- 1 & 3 pole MCCB 95mm² solid.
- Internal separation form 3A.
- 8, 12, 18 TP outgoing ways.
- Busbar rated current: 800A
- Busbar rated short time withstand current 35kA for 1x direct connection (unconditional).
- Single pole up to 125A - 70mm² flexible.
- Single pole up to 125A - 95mm² solid.
- Triple pole up to 250A -120mm² flexible.
630A/800A Incoming 125A/250A Outgoing - Glazed
Cat ref. ![]() | Description ![]() | ![]() | ||
---|---|---|---|---|
JF60204BG | 630A 6 Way 2*250A + 4*125A Glazed | |||
JF80204BG | 800A 6 Way 2*250A + 4*125A Glazed | |||
JF80206BG | 800A 8 Way 2*250A + 6*125A Glazed | |||
JF80404BG | 800A 8 Way 4*250A + 4*125A Glazed | |||
JF80210BG | 800A 12 Way 2*250A + 10*125A Glazed | |||
JF80408BG | 800A 12 Way 4*250A + 8*125A Glazed | |||
JF80414BG | 800A 16 Way 4*250A + 14*125A Glazed | |||
JF80612BG | 800A 18 Way 6*250A + 12*125A Glazed |
630A/800A Incoming 125A/250A Outgoing - Plain
Cat ref. ![]() | Description ![]() | ![]() | ||
---|---|---|---|---|
JF80204B | 800A 6 Way 2*250A + 4*125A Plain | |||
JF80206B | 800A 8 Way 2*250A + 6*125A Plain | |||
JF80404B | 800A 8 Way 4*250A + 4*125A Plain | |||
JF80210B | 800A 12 Way 2*250A + 10*125A Plain | |||
JF80408B | 800A 12 Way 4*250A + 8*125A Plain | |||
JF80414B | 800A 18 Way 4*250A + 14*125A Plain | |||
JF80612B | 800A 18 Way 6*250A + 12*125A Plain |
630A/800A Incomer Kits
No picture available
- A 300mm cable spreader box is recommended.
- For 800LBSÂ select the required 800A rated panelboard 50kA (e.g. JF80206BG) and add the suffix 800LBS e.g. JF80206BG800LBS
630A/800A Rated Pan Assemblies
No picture available
Cat ref. ![]() | Description ![]() | ![]() | ||
---|---|---|---|---|
JF812BPA | 800A 12 Way 125A Pan Assembly | |||
JF818BPA | 800A 18 Way 125A Pan Assy | |||
JF80210BPA | 800A 12 Way 2*250A + 10*125A Pan Assy | |||
JF80204BPA | 800A 6 Way 2*250A + 4*125A Pan Assy | |||
JF80206BPA | 800A 8 Way 2*250A + 6*125A Pan Assy | |||
JF80408BPA | 800A 12 Way 4*250A + 8*125A Pan Assy | |||
JF80414BPA | 800A 16 Way 4*250A + 14*125A Pan Assy | |||
JF80404BPA | 800A 8 Way 4*250A + 4*125A Pan Assy | |||
JF80612BPA | 800A 18 Way 6*250A + 12*125A Pan Assy |
DIN Extension Boxes
Cable Spreader Boxes
Cable spreader boxes are used for additional cabling space therefore do not require doors. If doors are desired optional door kits are available.
Side Meter Enclosures
Top/ Bottom Meter Enclosures
Corner Filler Enclosures
Data is subject to errors and technical modifications.